HL-C50/2-HX-Eaton Moeller series xPole – HL/HL-HX MCB
Roll over image to zoom in
194776 HL-C50/2
Miniature circuit breaker (MCB), 50 A, 2p, characteristic: C
Miniature circuit breaker (MCB), HL, xPole Home, 2-pole, tripping characteristic: C, rated current In: 50 A, rated switching capacity according to IEC/EN 60898-1: 4,5 kA, Switchgear for residential and commercial applications.
General specifications
Product name: Eaton Moeller series xPole - HL/HL-HX MCB
Part no.: HL-C50/2
EAN: 9010238062603
Product Length/Depth: 85 millimetre
Product height: 73 millimetre
Product width: 35.4 millimetre
Product weight: 0.24 kilogram
Compliances: RoHS conform
Product Tradename: xPole - HL/HL-HX
Product Type: MCB
Product Sub Type: None
Technical Data – Electrical
Voltage type: AC
Rated operational voltage (Ue) – max: 230 V
Rated insulation voltage (Ui): 440 V
Rated impulse withstand voltage (Uimp): 4 kV
Frequency rating – min: 50 Hz
Frequency rating – max: 60 Hz
Rated switching capacity (IEC/EN 60898-1): 4.5 kA
Rated short-circuit breaking capacity (EN 60898) at 230 V: 4.5 kA
Rated short-circuit breaking capacity (EN 60898) at 400 V: 4.5 kA
Rated short-circuit breaking capacity (IEC 60947-2) at 230 V: 0 kA
Rated short-circuit breaking capacity (IEC 60947-2) at 400 V: 0 kA
Overvoltage category: III
Pollution degree: 3
Technical Data – Mechanical
Width in number of modular spacings: 2
Built-in depth: 44 mm
Degree of protection: IP20
Connectable conductor cross section (solid-core) – min: 1 mm²
Connectable conductor cross section (solid-core) – max: 25 mm²
Connectable conductor cross section (multi-wired) – min: 1 mm²
Connectable conductor cross section (multi-wired) – max: 25 mm²
Additional information
part.no | HL-C50/2-HX |
---|---|
current | |
Short Circuit | 4.5 |
No of poles | 2 |
Reviews
There are no reviews yet.